Start-Up

25.

BASIC SETTING OF THE PROCESS
CONTROLLER

25.1.

P.CONTROL – Setting up and parameterization of
the process controller

To start up the process controller, you must make the following settings in the

P.CONTROL menu:

1.

SETUP

Set up the process controller (configuration)

2.

PID.PARAMETER

Parameterize process controller

Operating structure:

EXIT

EXIT

PID.PARAMETER

SETUP

DBND 0.1 %

PV-INPUT

KP 0.00

PV SCALE

TN 0.5

SP-INPUT

TV 0.0

SP-SCALE*

X0 0.0 %

P.CO-INIT

FILTER 0

P.CONTROL

ENTER

ENTER

ENTER

EXIT

*

The SP SCALE function is indicated only if the external set-point value default (external) menu option is activated under
SP INPUT
.

Figure 35:

Operating structure P.CONTROL

Key:.

Insensitivity range (dead band) of the PID process controller

..Amplification factor of the process controller

..Reset time

..Hold-back time

..Operating point

..Filtering of the process actual value input

..Indication of the signal type for process actual value (4 - 20 mA, frequency input, Pt 100 input)

..Specification of the physical unit and scaling of the process actual value

..Type of set-point value default (internal or external)

..Scaling of the process set-point value (only for external set-point value default)

..Enables a smooth switchover between AUTOMATIC and MANUAL mode

English

Type 8792, 8793