Input signals from the control centre (e.g. plc) – Burkert Type 8793 User Manual

Page 57

Advertising
background image

57

Installation

Type 8792, 8793

english

15.1. Connection board of the Type 8792/8793 with

screw-type terminals

1
2
3
4

+24 V

GND

83 +
85 +
31 +

32 –

11 +

12 –

81 +

S +
S –
A
B

Optional:

Figure 27:

Designation of the screw-type terminals

Procedure:

Unscrew the 4 screws on the housing cover and remove the cover.
The screw-type terminals are now accessible.

Connect Type 8792/8793.
The procedure is described in the following chapters.
for Type 8792: chapter “15.2. Terminal assignment for cable gland - positioner Type 8792”
for Type 8793: chapter “15.3. Terminal assignment for cable gland - process controller Type 8793”

15.2. Terminal assignment for cable gland - positioner

Type 8792

15.2.1. Input signals from the control centre (e.g. PLC)

Terminal

Configuration

On.the.device.side

External.circuit./.Signal.level

11 +

Set-point value +

11 +

+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated

12 –

Set-point value GND

12 –

GND set-point value

81 +

Binary input +

81 +

+

0 – 5 V (log. 0)
10 – 30 V (log. 1)

specific to operating voltage GND
(terminal GND)

Table 16:

Terminal assignment; input signals of the control centre