90

Start-Up

25.2.3.

SP-INPUT – Type of the set-point value default (internal or

external)

The SP-INPUT menu specifies how the default of the process set-point value is to be implemented.

• Internal:

Input of the set-point value on the process level

• External:

Default of the set-point value via the standard signal input

Operating structure:

ENTER

SELEC

EXIT

SP-INPUT

internal

external

Set-point value default, internal
Input the process set-point value on the process
level
Set-point value default, external
Default of the process set-point value via the
standard signal input

Figure 40:

Operating structure PV-INPUT

Specify.type.of.set-point.value.default.in.the.menu.SETUP.→.SP-INPUT:

Key

Action

Description

/

Select

SP-INPUT

ENTER

Press

The types of set-point value default are displayed.

/

Select the type of set-point
value default

SELEC

Press

The selection is marked by a filled circle .

EXIT

Press

Return to

SETUP.

Table 41:

SP-INPUT; specifying type of the set-point value default

For internal set-point value default (

SP-INPUTinternal), the process set-point value is input directly on

the process level.

25.2.4.

SP-SCALE – Scaling of the process set-point value

(for external set-point value default only)

The

SP-SCALE menu assigns the values for the lower and upper process set-point value to the particular current

or voltage value of the standard signal.
The menu is available for external set-point value default only (

SP-INPUT external).

For internal set-point value default (

SP-INPUTinternal), there is no scaling of the process set-point

value via

SPmin and SPmax.

The set-point value is input directly on the process level. The physical unit and the position of the decimal
point are specified during the scaling of the process actual value (

PV-SCALE PVmin).

For description see Chapter "25.2.2. PV-SCALE – Scaling of the process actual value", page 86

English

Type 8792, 8793