Basic setting of the device, Basic.setting.of.the.device – Burkert Type 8793 User Manual

Page 77

Advertising
background image

77

Start-Up

23.

BASIC SETTING OF THE DEVICE

The following settings must be made for the basic setting of Type 8792/8793:

1.

INPUT

Selection of the input signal (see Chapter "23.1").

2.

X.TUNE

Automatic self-parameterization of the position controller (see Chapter "23.2")

Operating structure for the basic setting:

INPUT

X.TUNE

4-20 mA

CARACT

Select

parameters

0-20 mA

P.CONTROL

0-10 V

0-5 V

DIAGNOSE

X.TUNE.CONFIG

M.TUNE.POS

M.TUNE.PWM

M.TUNE.AIR

Press for approx. 3 s

Hold.down
as long as
countdown
(5 ...) is
running

X.TUNE

STARTED

TUNE #0

INIT

X.TUNE

READY

Process.level (values are displayed)

Configuration

Select the input signal

Activating auxiliary functions *

Manual.TUNE, Manual parameterization
(not required for standard applications)

Automatic self-parameterization

MENU

Setting.level.
Main.menu.(MAIN)

EXIT

EXIT

ENTER

EXIT

ENTER

ENTER

SELEC

ENTER

SELEC

RUN

RUN

press.
briefly

EXIT

ADD.FUNCTION

EXIT

EXIT

* required only for start-up of the process controller (see Chapter "24. Activation of the process controller")

Figure 32:

MAIN – main menu, operating structure in as-delivered state

English

Type 8792, 8793

Advertising
This manual is related to the following products: