Burkert Type 8793 User Manual

Page 169

Advertising
background image

169

Auxiliary functions

26.3.1. Description of the menu for the manual configuration of

X.TUNE

X.TUNE.CONFIG

Configuration.of.the.X.TUNE.
function

Specify which functions are to be executed when
X.TUNE is running (automatic self-optimization).

M.TUNE.POS

Position.of.the.end.positions

- Specify whether the pneumatic actuator has

mechanical end positions.

- Manual specification of the end positions

If there are no mechanical end positions available,
these are not approached by the

X.TUNE and must

be manually specified.

M.TUNE.PWM

Optimization.of.the.PWM.signals Manual optimization of the PWM signals for control

of the aeration valves and bleed valves.

For optimization the valves must be aerated and
bled. A progress bar on the display indicates the
speed at which the valve is aerated or bled.
The setting is optimum when the progress bar
moves as slowly as possible.

M.TUNE.AIR

Determination.of.the.opening.
and.closing.times.of.the.actuator

Continuous determination of the opening and
closing times of the actuator.

26.3.1.1.

X.TUNE.CONFIG – Configuration of the X.TUNE function

In this menu you can specify which functions are to be executed when the

X.TUNE function is running

automatically.
Specifying.the.functions.in.X.TUNE.CONFIG

Key

Action

Description

/

Select

X.TUNE.CONFIG

ENTER

Press

The functions for automatic self-parameterization by

X.TUNE are

displayed.

/

Select required function

SELEC

Press

Activate the function by checking the box .

Select all required functions in succession using the arrow
keys / and
activate by checking the box .

EXIT

Press

Return to the

Manual.TUNE menu.

Table 95:

X.TUNE.CONFIG; specifying the functions for automatic self-parameterization by X.TUNE

english

Type 8792, 8793

Advertising
This manual is related to the following products: