DeviceNet

33.6. Configuration example 2

This example describes the principle procedure for setting up the process image of a DeviceNet master/scanner
using the software

RSNetWorx for DeviceNet (Rev. 4.12.00).

Setting.up.the.scan.list.and.setting.the.I/O.parameters

First of all set up the

scan list of the DeviceNet master/scanner.

To do this, include the devices listed in the left part of the associated window in the scan list in the right part of
the window.

Then the I/O parameters can be changed for each device included in the scan list.
This is required if assemblies which differ from the default settings were selected during configuration of the
device in question.

“Figure 132” shows the setting of the I/O parameters when
-..Input.assembly..

POS+CMD+ERR (5 bytes long) is selected and when

-..Output.assembly

INP (2 bytes long; default assembly - no change required) is selected

Figure 132: Screenshot - DeviceNet - Setting of I/O parameters