Burkert Type 8793 User Manual

Page 79

Advertising
background image

79

Start-Up

23.2.

X.TUNE – Automatic adjustment of the position

controller

WARNING!

Danger.due.to.the.valve.position.changing.when.the.X.TUNE.function.is.run!

When the

X.TUNE function is run under operating pressure, there is an acute risk of injury.

Never run X.TUNE while the process is running!

• Secure system against unintentional activation!

NOTE!.

An.incorrect.supply.pressure.or.incorrectly.connected.operating.medium.pressure.may.cause.the..
controller.to.be.wrongly.adjusted!

Run X.TUNE in.each.case.at the supply pressure available in subsequent operation (= pneumatic auxiliary
power).

• Run the

X.TUNE function preferably without operating medium pressure to exclude interference due to flow

forces.

The following functions are actuated automatically:

• Adjustment of the sensor signal to the (physical) stroke of the actuator used.

• Determination of parameters of the PWM signals to control the solenoid valves integrated in type 8792/8793.

• Adjustment of the controller parameters for the position controller. Optimization occurs according to the criteria

of the shortest possible transient time without overshoots.

Procedure:

Key

Action

Description

MENU

Press

for approx. 3 s

Switching from process level

setting level.

/

Select X.TUNE

RUN

Hold down

as long as countdown (5 ...) is
running

While the automatic adjustment is running, messages on the
progress of the

X.TUNE

(e.g.

"TUNE #1....") are indicated on the display.

When the automatic adjustment ends, the message "X.TUNE READY"
is indicated.

Press any key

Return to the main menu (MAIN).

EXIT

Press

Switching from setting level

process level.

Table 34:

Automatic adjustment of X.TUNE

To stop

X.TUNE, press the left or right selection key

STOP

.

English

Type 8792, 8793

Advertising
This manual is related to the following products: