Auxiliary functions

26.2.15.

CAL.USER – Calibration of actual value and set-point value

The following values can be manually calibrated with this function:

• Position actual value calibr. POS (0 - 100 %)

• Position set-point value calibr. INP (4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)

For the calibration process the signal type is displayed which was specified for the input signal.
See Chapter “23.1. INPUT - Setting the input signal”.

Type.8793:

The following values can be calibrated only for Type 8793 and activated process controller (

P.CONTROL).

• Process set-point value calibr. SP (4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)

For the calibration process the signal type is displayed which was specified for the input signal.
See Chapter “23.1. INPUT - Setting the input signal”.

The calibration of the process set-point value is only possible if the external set-point value default was
selected when setting up the process controller.
See Chapter “25.2.3. SP-INPUT – Type of the set-point value default (internal or external)”.
Setting:

P.CONTROLSETUPSP-INPUTexternal

• Process actual value calibr. PV (4 - 20 mA or *C)

For the calibration process the signal type is displayed which was specified for the process actual value when
setting up the process controller.
See Chapter “25.2.1. PV-INPUT – Specifying signal type for the process actual value”

The frequency signal type (flow rate) cannot be calibrated.
If the frequency was set when setting up the process controller (

P.CONTROLSETUPPV-INPUT

Frequency), the calibr. PV menu option is hidden.