DeviceNet

31.5. Bus status display

The bus status is indicated on the display on the device.

Display
(is displayed approx.
every 3 seconds)

Device.status

Explanation

Troubleshooting

BUS offline

Offline

Device is not connected to the
bus.

The network access procedure
(Duplicate MAC-ID-Test,
duration approx. 2 s) has still
not ended.

The device is the only active
network node.

• Check whether the baud

rate has been correctly set
network-wide.

• Bus connection including

plug assignment correct.

• Check operating supply and

bus connection of the other
nodes.

BUS no connection

Online,

no connection to
the master

Device is connected correctly to
the bus, the network access pro-
cedure has ended without errors,
however there is no established
connection to the master.

• New connection established

by master.

BUS timeout

I/O connection
timeout

An I/O connection is in the
TIME OUT state.

• New connection established

by master.

• Ensure that I/O data is

transferred cyclically or, if
COS confirmed, that cor-
responding Acknowledge
messages are sent by the
master.

BUS critical err

Critical bus error

Other device with the same
address in the network.

BUS offline due to communi-
cation problems.

• Change address of the

device and restart device

• Error analysis in the network

with a bus monitor.

Table 111:

Bus status display; DeviceNet