Configuration example 1, Installation of the eds file, Address assignment – Burkert Type 8793 User Manual

Page 223: . configuration.example.1

Advertising
background image

223

DeviceNet

33.5. Configuration example 1

The example describes the principle procedure when configuring the device using the software

RSNetWorx for

DeviceNet (Rev. 4.12.00).

33.5.1. Installation of the EDS file

The EDS file supplied on the CD is installed with the aid of the EDS Installation Wizard Tool associated with
RSNetWorx.

During the installation procedure the icon also supplied on CD can be assigned (if this does not occur automatically).

33.5.2. Address assignment

There are two options of assigning an address to the devices.

• The address can be set by pressing the operator keys on the device to the required value within the range 0 – 63

(see chapter “33.3. BUS.COMM – Settings on Type 8792/8793”).

• with the aid of the Tools Node Commissioning belonging to RSNetWorx the address of connected devices can

be changed via the bus. Therefore devices with the default address 63 can also be inserted sequentially into an
existing network without difficulty.

The following image indicates how the new address 2 is assigned to a device with address 63.

Figure 129: Screenshot - DeviceNet - Address assignment

english