Auxiliary functions

Display.TEMP.CHECK

Description.of.the.functions

EXIT

29-8-1

TEMP.CHECK

CURRENT

MAX

MIN

LIMIT

21.7 *C

21.7 *C

21.7.*C

CURRENT indicates the current temperature.
MAX indicates the highest temperature of the slave pointer
MIN indicates the lowest temperature of the slave pointer
The permitted temperature range can be changed in the

LIMIT submenu.

A message is output if the temperature goes outside the permitted range.
The temperature range has been preset at the factory from 0 ... 60 °C.

The history entries of the last 3 messages can be viewed and deleted in
the

HISTORY submenu.

EXIT

ENTER

29-8-1

LIMIT

HISTORY

Table 88:

TEMP.CHECK; temperature range

Operating structure:

ENTER

INPUT

INPUT

ENTER

OK

ESC

EXIT

CLEAR

Input

Limit

History entry is

displayed

Lowest temperature of the slave pointer

Highest temperature of the slave pointer

Display of the current temperature

TEMP.CHECK

TEMP.MAX

TEMP.MIN

LIMIT

HISTORY

Delete.history.entry

EXIT

MIN

MAX

CURRENT

CLEAR

CLEAR

Delete.value

Delete.value

EXIT

Figure 96:

Operating structure TEMP.CHECK

Specifying.temperature.limit.for.the.output.of.messages

Key

Action

Description

/

Select

TEMP.CHECK

(To do this, the

TEMP.CHECK function must be incorporated into

the

DIAGNOSE main menu. See Chapter “26.2.22.4. Activation of

diagnosis functions”).

ENTER

Press

The menu is displayed.

/

Select

LIMIT

ENTER

Press

The upper and lower temperature limit is displayed.
The upper limit

TEMP.MAX has already been selected.

INPUT

Press

Open input screen for upper temperature limit.

english

Type 8792, 8793