Changing the operating state, Safety settings if the bus fails, Bus status display – Burkert Type 8793 User Manual

Page 191: . changing.the.operating.state, . safety.settings.if.the.bus.fails, . bus.status.display

Advertising
background image

191

PROFIBUS DP

28.3. Changing the operating state

There are two ways of switching between the MANUAL and AUTOMATIC operating states for the PROFIBUS DP:

• Input via the keyboard on the device:

On the process level using the key function

MANU

and

AUTO

.

• The operating state is transferred to the device via the bus (under

PDO MODE).

In this case switching is no longer possible using the keyboard on the device.

28.4. Safety settings if the bus fails

The position is approached which corresponds to the set-point value last transferred (default setting).

Other setting options (see chapter “30.3. BUS.COMM – Settings on Type 8792/8793”.

28.5. Bus status display

The bus status is indicated on the display on the device.

Display

Device.status

Explanation

Troubleshooting

BUS offline

is displayed approx. every
3 seconds

offline

Device is not connected to the
bus

• Check bus connection

including plug assignment.

• Check operating voltage

and bus connection of the
other nodes.

Table 99:

Bus status display; PROFIBUS DP

28.6. Differences between the field bus devices and

devices without a field bus

The.following.chapters.of.these.operating.instructions.are.not.valid.for.Type.8792/8793.with..
PROFIBUS.DP.

• Section “Installation”

Chapter “14. Electrical connection -
Circular plug-in connector version (multi-pole version)”


Chapter„ “15. Electrical connection - Terminal version for cable gland”

• Section “Start-up”

Chapter “23.1. INPUT - Setting the input signal”

• Section “Auxiliary functions”

Chapter “26.2.5. SPLTRNG – Signal split range”

Chapter “26.2.15. CAL.USER – Calibration of actual value and set-point value”
- Menu option

calibr.INP, calibration of the position set-point value

- Menu option

calibr.SP, calibration of the process set-point value

english

Type 8792, 8793

Advertising