Static output assemblies – Burkert Type 8793 User Manual

Page 222

Advertising
background image

222

DeviceNet

33.4.2. Static output assemblies

Name

Address of data attribute of the assemblies
for read access. Class, Instance, Attribute

Format of the

data attribute

INP (factory setting)

4, 21, 3

Byte 0: INP low

Byte 1: INP high

SP

4, 22, 3

Byte 0: SP low

Byte 1: SP high

Table 121:

Static output assemblies; DeviceNet

The addresses indicated in “Table 121” can be used as path data for the attribute

Consumed Connection Path of

an I/O connection.

The attributes described in more detail in the following “Table 122” can be transferred as output process data via
this I/O connection.

Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed acycli-
cally via

Explicit Messages.

Name

Description of the output data attributes

Attribute Address Class,
Instance, Attribute; Data
type, Length

INP

Nominal position

Set-point value of positioner as ‰. Value range 0 – 1000.

In “pure” position controller mode (

P.CONTROL inactive) the

transfer of the nominal position

INPUT is required; as a process

controller (

PCONTROL active) the transfer of INPUT is not

possible.

If the value is too small or too large, the last valid value is used and
is indicated in

ERR with HEX 14.

111, 1, 58;

UINT, 2 byte

SP *

Process set-point value

Set-point value of process controller in physical unit (as set in the
menu

P.CONTROL SETUP SP-INPUT or SP-SCALE), max.

value range -999 – 9999, depending on internal scaling.

If the value is too small or too large, the last valid value is used and
is indicated in

ERR with HEX 15.

120, 1, 2;

INT, 2 byte

* relevant only for Type 8793 and when process controller activated.

Table 122:

Iutput data attributes; DeviceNet

english

Type 8792, 8793

Advertising
This manual is related to the following products: