Procedure for inputting the parameters – Burkert Type 8793 User Manual

Page 93

Advertising
background image

93

Start-Up

25.3.

PID.PARAMETER – Parameterizing the process

controller

The following control parameters of the process controller are manually set in this menu.

DBND 1.0 %

Insensitivity range (dead band) of the process controller

KP 1.00

Amplification factor of the (P-contribution of the PID controller)

TN 999.0

Reset time (I-contribution of the PID controller)

TV 0.0

Hold-back time (D-contribution of the PID controller)

X0 0.0 %

Operating point

FILTER 0

Filtering of the process actual value input

The automatic parameterization of the PID controller integrated in the process controller
(menu options

KP, TN. TV) can be implemented with the aid of the P.TUNE function

(see Chapter "25.5. P.TUNE – Self-optimization of the process controller").

Basic information for setting the process controller can be found in Chapters "40. Properties of PID Con-
trollers"

and "41. Adjustment rules for PID Controllers".

25.3.1. Procedure for inputting the parameters

The settings in the

PID.PARAMETER menu are always made in the same way.

Procedure:

Key

Action

Description

/

Select

PID.PARAMETER

ENTER

Press

The menu for parameterizing the process controller is displayed.

/

Select menu option

INPUT

Press

The input screen is opened.

/

Increase value
Reduce value

or

<–

Select decimal place
Increase value

Set value when
* DBND X.X % / X0 0 % / FILTER 5 :

Set value when
* KP X.XX / TN X.0 sec / TV 1.0 sec :

OK

Press

Return to

PID.PARAMETER.

EXIT

Press

Return to

P.CONTROL.

EXIT

Press

Return to the main menu (MAIN).

EXIT

Press

Switching from setting level

process level.

*

The description of the submenus of PID.PARAMETER can be found in the following chapters.

Table 44:

PID.PARAMETER; parameterizing process controller

If the submenu is left by pressing the left selection key

ESC

, the value remains unchanged.

English