DeviceNet

32.

ELECTRICAL CONNECTIONS

DANGER!

Risk.of.injury.due.to.electrical.shock!

• Before reaching into the device or the equipment, switch off the operating voltage and secure to prevent

reactivation!

• Observe applicable accident prevention and safety regulations for electrical equipment!

Risk.of.explosion.if.used.in.Ex.area!

To avoid the risk of explosion, connect the Ex device to the power supply as described below:

• Secure cable connections, which use circular connectors, with suitable locking clips.

(For example: EXCLIP, FA. Phoenix Contact,

Type SAC-M12-EXCLIP-M, Art. no. 1558988 or
Type SAC-M12-EXCLIP-F, Art. no. 1558991.

• Use only cable and line entry points which have been approved for the respective application area. Screw

cable and line entry points into place according to the associated installation instructions.

• Install pre-assembled cable glands according to the installation instructions supplied by the cable gland

manufacturer.
Before start-up in the Ex area, check whether the cable gland was installed as described in these installation
instructions.

• Close all unnecessary cable glands with lock screws approved for the explosions area.

WARNING!

Risk.of.injury.from.improper.installation!

• Installation may be carried out by authorized technicians only and with the appropriate tools!

Risk.of.injury.from.unintentional.activation.of.the.system.and.an.uncontrolled.restart!

• Secure system from unintentional activation.

• Following installation, ensure a controlled restart.

For operation of the device the following must always be connected:

X1 - circular connector M12, 8-pole (for operating voltage see “Table 112: Pin assignment; X1 - M12, 8-pole
circular connector DeviceNet” and

X3 - circular connector M12, 5-pole, (see “Table 113: Pin assignment; X3 - M12, 5-pole circular connector -
bus connection; DeviceNet”)

NOTE!

Electromagnetic.compatibility.(EMC).is.only.ensured.if.the.appliance.is.connected.correctly.to.an.
earthing.point.

On the outside of the housing is a TE terminal for connection of the technical earth (TE).

• Connect the TE terminal to the earthing point via a shortest possible cable (maximum length 30 cm).

english

Type 8792, 8793