Combination with valve types and mounting versions – Burkert Type 8793 User Manual

Page 14

Advertising
background image

14

Description of System

• Mounting.

on linear actuator according to NAMUR recommendation (DIN IEC 534 T6) or on rotary actuator according to
VDI/VDE 3845.

• Optional.

Remote version for DIN rail mounting or for mounting bracket

6.1.2.

Combination with valve types and mounting versions

The positioner Type 8792 / process controller Type 8793 can be mounted on different continuous valves. For
example on valves with piston, membrane or rotary actuator. The actuators can be single-acting or double-acting.

• For single-acting actuators, only one chamber is aerated and deaerated during actuation. The generated

pressure works against a spring. The piston moves until there is an equilibrium of forces between compressive
force and spring force. To do this, one of the two air connections must be sealed with a threaded plug.

• For double-acting actuators the chambers on both sides of the piston are pressurised. In this case, one

chamber is aerated when the other one is deaerated and vice versa. In this design, no spring is installed in the
actuator.

Two basic device versions are offered for the positioner Type 8792 / process controller Type 8793; they differ in
the attachment option and in the position sensor.
Device.version.1:

An internal position sensor is used which is designed as a rotary potentiometer.
Type 8792/8793 is mounted directly on the actuator or attached to the side.
Device.version.2:.
An external position sensor (linear or rotative) via a digital interface.
The Type 8792/8793 is attached to a wall either with a DIN rail or with a mounting bracket (remote design).

English

Types 8792, 8793

Advertising
This manual is related to the following products: