Burkert Type 8793 User Manual

Page 80

Advertising
background image

80

Start-Up

Operating structure:

X.TUNE

INPUT

Press for approx. 3 s

Hold.down
as long as
countdown
(5 ...) is
running

X.TUNE

STARTED

TUNE #0

INIT

X.TUNE

READY

Process.level (values are displayed)

Automatic
self-parameterization

MENU

Setting.level

RUN

EXIT

ADD.FUNCTION

EXIT

Figure 34:

Operating structure X.TUNE

Automatically.determining.dead.band.DBND.by.running.X.TUNE:

When

X.TUNE is running, the dead band can be automatically determined depending on the friction

behavior of the actuating drive.
Before running

X.TUNE, the X.CONTROL auxiliary function must be activated by incorporating it into the

main menu (MAIN).
If

X.CONTROL is not activated, a fixed dead band of 1 % is used.

The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key

EXIT

. During the save process, the save

symbol is indicated on the display.

Possible.error.messages.when.running X.TUNE:

Display

Causes.of.error

Remedial.action

TUNE
err/break

Manual termination of self-parameterization
by pressing the

EXIT

key

X.TUNE locked

The

X.TUNE function is blocked

Input access code

X.TUNE
ERROR 1

No compressed air connected

Connect compressed air

X.TUNE
ERROR 2

Compressed air failed during Autotune
(

X.TUNE).

Check compressed air supply

X.TUNE
ERROR 3

Actuator or control system deaeration side
leaking

Not possible, device defective

English

Type 8792, 8793

Advertising
This manual is related to the following products: