Description and features of the type 8792/8793, General description, Features – Burkert Type 8793 User Manual

Page 13: Description.and.features.of.the.type.8792/8793, . general.description

Advertising
background image

13

Description of System

6.

DESCRIPTION AND FEATURES OF THE
TYPE 8792/8793

6.1.

General description

The positioner Type 8792 / process controller Type 8793 is a digital, electro-pneumatic position controller for
pneumatically actuated continuous valves. The device incorporates the main function groups

- Position sensor

- Electro-pneumatic control system
- Microprocessor electronics

The position sensor measures the current positions of the continuous valve.
The microprocessor electronics continuously compare the current position (actual value) with a set-point position
value specified via the standard signal input and supplies the result to the positioner/process controller.
If there is a control difference, the electro-pneumatic control system corrects the actual position accordingly.

6.1.1.

Features

• Models

- Positioner (position controller) Type 8792
- Process controller with integrated position controller, Type 8793.

• Position.sensors.

- internal high resolution conductive plastic potentiometer or
- external non-contact, non-wearing position sensor (remote).

• Microprocessor-controlled.electronics

for signal processing, control and valve control.

• Operating.module.

Operation of the device is controlled by four keys. The 128 x 64 dot matrix graphics display enables you to
display the set-point or actual value and to configure and parameterize via menu functions.

• Control.system.

The control system consists of 2 solenoid valves and 4 diaphragm reinforcers. In single-acting actuators the
working connection 2 must be sealed with a threaded plug.

• Feedback.(optional).

The feedback is implemented either via 2 proximity switches (initiators), via binary outputs or via an output
(4 – 20 mA / 0 – 10 V).
When the valve reaches an upper or lower position, this position can be relayed e.g. to a PLC via binary outputs.
The operator can change the initiators or limit positions via control lugs.

• Pneumatic.interfaces.

Internal thread G1/4“

• Electrical.interfaces.

Circular plug-in connector or cable gland

• Housing.

Plastic-coated aluminium housing with hinged cover and captive screws.

English

Types 8792, 8793

Advertising
This manual is related to the following products: