Dbnd – insensitivity range (dead band) – Burkert Type 8793 User Manual

Page 94

Advertising
background image

94

Start-Up

25.3.2.

DBND – Insensitivity range (dead band)

This function causes the process controller to respond from a specific control difference only. This protects both
the solenoid valves in Type 8792/8793 and the pneumatic actuator.

Factory setting: 1.0 % with reference to the range of the scaled process actual value

(setting in the menu

PV-SCALE PVminPVmax).

Operating structure:

EXIT

Input value

ENTER

INPUT

OK

ESC

PID.PARAMETER

DBND 1.0 %

FILTER 0

Figure 43:

Operating structure DBND; insensitivity range

Insensitivity range for process control

Process
set-point value
(SP)

Control
difference

Xd2

Process
actual value
(PV)

Xd2

Xd2‘

Xd2‘

to the controller

Dead band

Figure 44:

Diagram DBND; insensitivity range for process control

25.3.3.

KP – Amplification factor of the process controller

The amplification factor specifies the P-contribution of the PID controller
(can be set with the aid of the

P.TUNE function).

Factory setting: 1.00

Operating structure:

EXIT

Input value

ENTER

INPUT

OK

ESC

PID.PARAMETER

KP 1.00

FILTER 0

DBND 1.0 %

Adjustment range: 0 ... 99.99
(% / set unit)

Figure 45:

Operating structure KP; amplification factor

The

KP amplification of the process controller refers to the scaled, physical unit.

English

Type 8792, 8793