Start-Up

25.2.

SETUP – Setting up the process controller

These functions specify the type of control.

The procedure is described in the following Chapters "25.2.1" to "25.2.5".

25.2.1.

PV-INPUT – Specifying signal type for the process actual

value

One of the following signal types can be selected for the process actual value:

• Standard signal

4 ... 20 mA

flow rate, pressure, level

• Frequency signal

0 ... 1000 Hz

flow rate

• Circuit with Pt 100

-20 °C ... +220 °C

temperature

Factory setting: 4 ... 20 mA

When the operating voltage has been switched on, the device looks for connected sensor types
(automatic sensor detection).
When a sensor type (PT 100 or 4 ... 20 mA) is detected, the signal type is automatically implemented in the
PV-INPUT operating menu.
If no sensor signal is detected, the last setting is retained.

The signal type frequency signal cannot be detected automatically, but must be set manually in the
PV-INPUT menu.

Operating structure:

ENTER

SELEC

EXIT

PV-INPUT

4-20 mA

Frequency

PT 100

Standard signal 4–20 mA
(flow rate, pressure, level)

Frequency signal 0 ... 1000 Hz
(flow rate)

Circuit with Pt 100
(temperature) -20 °C ... +220 °C

Figure 36:

Operating structure PV-INPUT

Specifying.signal.type.in.the.menu.SETUP.→.PV-INPUT:

Key

Action

Description

/

Select

PV-INPUT

ENTER

Press

The signal types are displayed.

/

Select signal type

SELEC

Press

The selected signal type is now marked by a filled circle .

EXIT

Press

Return to

SETUP.

Table 38:

PV-INPUT; Specifying signal type