5 - 94

After “AND 0 S0” (stack falls):

S1: 1 (S1 remains the same after the shift down)
S0: 1
R: 0

After “OR 0 S0” (stack falls):

S1: 1
S0: 1
R: 1

After “OUT 101 D0_1”:

S1: 1
S0: 1
R: 1

The ladder diagram can be constructed differently to simplify the programming.

DI_8

8

DI_1

101

DI_11

11

DI_9

9

DI_10

10

8

DI_8

9

DI_9

11

DI_11

12

DI_12

10

DI_10

0

S0

101

DO_1

LOAD

AND
LOAD

OR
AND
OR
OUT

DI_12

12

In fact, most rungs can be simplified to require only one additional “LOAD” (other than the opening
“LOAD”) and one operation with the “S0” register (i.e., the “S1” register would not be needed).

The Latches

There are four latches that are available with the PLC. Each has two inputs and one output. The output
reflects the state of the latch, either “1” (ON) or “0” (Off). When the set input is “1” (true), the state of the
latch (the output) will be “1” (On). When the reset input is “1” (true), then the state of the Latch will be “O”
(Off). The set and reset inputs need only be true for one scan. The latch will retain its state (while the power
is “On”) until the opposite input becomes true. If both inputs are “1” (true) at the same time, the state of the
latch will be “0” (Off).

The set inputs (act as coils) are labelled:

Lch1 Set (PLC Bit 116)
Lch2 Set (PLC Bit 117)
Lch3 Set (PLC Bit 118)
Lch4 Set (PLC Bit 119)