8 - 22

ANALOG OUTPUT TESTS P2/3

The Analog Output screen displays the Monitor Parameters that monitor the Auxiliary Analog Output. Set the
AO Parameter (CP-290) to “0 ” and depending on the AO Mode (CP-291), either enter a voltage or a
current in AO Direct (CP-465). Measure the voltage or the current on the output to confirm the setting. Be
sure to return the AO Parameter to its previous value when the test is completed and set AO Direct back to
“0”.

AO Parameter

Analog Output Parameter (CP-290) identifies the Monitor or Control Parameter that is used for the Auxiliary Analog
Output. When the Analog Output Parameter (CP-290) is set to “0”, the value of AO DIRECT (CP-365) is used as the
output.

AO Direct

Analog Out Direct (CP-465) is the value output (in volts or milliamps) at the Auxiliary Analog Board's analog output
when the AO Parameter (CP-290) is set to a “0”.

AO Bits

Analog Output Bits (MP-166) displays the present value, in DAC Bits, of the Auxiliary Analog Output.

AO Signal

Analog Output Signal (MP-167) displays the present value, in either volts or milliamps of the Auxiliary Analog Output,
relative to AO Mode (CP-291).

AO Mode

Analog Output Mode (CP-291) identifies the mode of operation and calibration that are used for the Auxiliary Board
Analog Output signal.

2 = Current
1 = Voltage (default)