Appendix C: Parameter Summary Numeric Quick Reference (continued)

CP-375 Std Alm Msk

The Standard Alarm Mask (CP-375) allows you to mask out specific alarms so that they will not cause the ‘Alm’ indicator
to flash (in the lower left-hand corner of the CX-1200 screen) by entering a “0” in the corresponding bit position (see
figure below). You can also activate any of these alarm conditions by entering a “1” in the corresponding bit position.

Drive No Resp

Fb@MaxHz

CO_Sig@Max

Not In Use

Not In Use

Not In Use

Not In Use

MaxSpdLmt

Minimum Value: 00000000

Maximum Value: 11111111

Default Value: 00000000

Units: Coded

CP-376 CustAlm Msk

Custom Alarm Mask (CP-376) allows you to mask out the compare results so that they will not cause the ‘Alm’ indicator
to flash (in the lower left-hand corner of the CX-1200 screen) by entering a “0” in the corresponding bit position (see
figure below). You can also activate any of these compare conditions by entering a “1” in the corresponding bit
position.

Cmpr1 Out

Cmpr2 Out

Cmpr3 Out

Cmpr4 Out

Cmpr1 Out (Not)

Cmpr2 Out (Not)

Cmpr3 Out (Not)

Cmpr4 Out (Not)

Minimum Value: 00000000

Maximum Value: 11111111

Default Value: 00000000

Units: Coded