7 - 35

CX-1200 Serial Communications Binary Data-Link Protocol

(Message Transmission / Response Structures)

STX

BYTE

Length

BYTE

Address

BYTE

Function

BYTE

Message Error

BYTE

Data Field

Defined later for each function type

ETX

BYTE

CRC

WORD (2 BYTES)

Valid Binary Protocol Functions:

1)

Data Read Single Parameter

2)

Data Write Single Parameter

3)

Data Read Parameter Block (Limit 16)

4)

Data Write Parameter Block (Limit 16)

5)

Control Commands

6)

PLC Program Download from Control

7)

PLC Program Upload to Control

8)

Custom Engineering Units Download

9)

Custom Engineering Units Upload

10) Data Read Constant Table (Limit 6)
11) Parameter Data Trace Enable/Disable (enables/disables the CX-1200's ability to collect data

traces)

12) Data Read Parameter Trace (read consecutive trace data from the CX-1200)
13) Data Read Trace Status Byte

Example:
Request for CP-210

Table 38 Data Read Single Parameter, Host Transmission

STX

LEN

ADDR

FUNC

DATA

ETX

CRC

02

09

01

01

00D2

03

0C56