Appendix B: Formulas (continued)

The equations used to scale the Frequency Input 2 signal are given by:

MP-06 = MP-03 * CP-268 * X Seconds

s

CP-267 CP-209

written with parameter text:

Fb EU/Tm = FI2 Hz * EU FI2

1

* X Seconds

Pulses FI2 Time Base

where X = 1 for CP-209 = 0, None

X = 1 for CP-209 = 1, Second
X = 60 for CP-209 = 2, Minute
X = 3600 for CP-209 = 3, Hour

FI2 EU/Tm (MP-06) given in EU/Tm is multiplied by the ratio (given by CP-220) to obtain the desired speed in follower
applications.

MP-04 = MP-03 * 1 Rev * 60 Seconds

CP-266 Minute

written with parameter text:

FI2 RPM = FI2 Hz * 1 * 60 Seconds

PPR FI2 Minute

MP-20 = Follower Counts * X Pulses (CP-265) * CP-268

Count

CP-267

written with parameter text:

Fb Posn = FI2 Cnts * X Pulses (CP-265) * EU FI2

Count Pulses FI2

where

X = 1 for CP-265 = 1, Quad (quadrature mode)
X = 4 for CP-265 = 2, Incr (incremental mode)

Keep in mind that the scaling is included in the ratio calculation for more accurate results. This further justifies using
integers when possible for the scaling numbers.