13. How to Reset an

Absolute Encoder

208

13.4 Simple absolute Unit for PSEL Controller (Option)

Perform an absolute reset for following conditions:

x

Connect to PSEL controller after starting simple absolute unit

x

Disconnect encoder cable of actuator from PSEL controller and reconnect them

x

Error No. 41C "ABS unit encoder error (2)", and Error No.41D "ABS unit encoder error (3)" has occurred

x

Possible changes on home position, such as modifying home return and axis behavior related

parameter (No.1,6,10,11,12,21,38,42,43,44,46,47,50,51,66,67,68, Driver parameter No.26)

Please follow the instructions below to perform Absolute Reset by using "PC Software for X-SEL".

13.4.1 Instructions of Absolute Reset

(1) Supply main power (DC24V) to controller and simple absolute unit.

If there is no adjustment item besides "ABS unit encoder error (2)", 7 seg LED will display "E41C" when

panel unit is connected.

(2) Connect "PC Software for X- SEL" on online (Controller and PC with original connection cable).

(3) [Connection confirmation] dialog box will appear on screen. Configure connection port to your PC, then

click [OK] button. (Baud rate will be recognized automatically)

Fig. 14.67 Connection Confirmation Screen