1. Fundamental
2. Third Harmonic
3. Distorted Waveform

Effect of the sum of 2 multiple frequencies.


In the mains voltage, the fundamental has a frequency of 50 Hz, the second harmonic has
a frequency of 100 Hz, the third harmonic has a frequency of 150 Hz and so on.

Harmonic

distortion is a constant problem and should not be confused with short events such as
sags, surges or fluctuations.
It can be noted that in (1) the index of the sigma is from 1 to the infinite. What happens in
reality is that a signal does not have an unlimited number of harmonics: a number always
exists after which the harmonics value is negligible. The EN 50160 standard recommends
to stop the index in the expression (1) in correspondence of the 40

th

harmonic.




A fundamental element to detect the presence of harmonics is THD defined as:


1

40

2

2

V

V

THDv

h

h

=

=





This index takes all the harmonics into account. The higher it is, the more distorted the
waveform gets.