SIRIUS89N

EN - 52

6.5.3. "2-W", "3-W" and "

ρ" faulty cases

EARTH 05.06.01

Disconnect the External
Power Supply Adapter

If the instrument detect
the External Power
supply adapter
connected to instrument
will show the message
displayed to side.


- - -

Vd= ---V



Test:04
RAVG=0.74

o REMOVE POWER


3-W

!

FUNC CLR

EARTH 05.06.01

Warning symbol: Voltage
noise in input.

If the Instrument detect
a voltage values higher
than 5V the instrument
will shows the screen
displayed alongside.


o - - -

Vd= 230V



Test:04
RAVG=0.74

o VOLT IN INPUT


3-W

!

FUNC CLR

EARTH 05.06.01


- - -

Vd= 1V



Test:04
RAVG=0.74

o Rc HIGH


3-W

!

FUNC CLR

Message "Rc": Check
Auxiliary Earth rods.

The message "

Rc

high" indicates that the
instrument can't flow
the minimum current
necessary for
measurement. Check
that the terminals are
correctly connected
and the Auxiliary earth
rod connected to B4
(blue conductor) has
not been inserted in a
pebbly or poor
conductive ground. If
necessary pour some
water around the rod.