HT instruments SIRIUS89N User Manual

Page 94

Advertising
background image

SIRIUS89N

EN - 92

EN50160

ANALYZER CONFIG:

All the parameters:

unmodified

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MANU
Integration period:

10min

Recording of harmonics:

ON

Recording of Voltage anomalies (voltage Dips and Surge) :

ON

Voltage Reference for Dips and Surge detection:

230V

Upper Limit for Dips and Surge detection:

6%

Lower Limit for Dips and Surge detection:

10%

Selected voltages:

V1

Selected voltage harmonics:

THD, DC, 01, 02, 03, 04, … 25

CO-GENERATION: OFF

SURGES & DIPS

ANALYZER CONFIG:

All the parameters:

unmodified

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MANU
Integration period:

1min

Recording of harmonics:

OFF

Recording of Voltage anomalies (voltage Dips and Surge) :

ON

Voltage Reference for Dips and Surge detection:

230V

Upper Limit for Dips and Surge detection:

6%

Lower Limit for Dips and Surge detection:

10%

Selected voltages:

V1

Selected current:

I1

CO-GENERATION: OFF

HARMONICS

ANALYZER CONFIG:

All the parameters:

unmodified

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MANU
Integration period:

10min

Recording of harmonics:

ON

Recording of Voltage anomalies (voltage Dips and Surge) :

OFF

Selected voltages:

V1

Sel. Harmonics voltage : THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
Selected current:

I1

Sel. Harmonics current: THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
CO-GENERATION: OFF