HT instruments SIRIUS89N User Manual

Page 87

Advertising
background image

SIRIUS89N

EN - 85

8.7.2. "METER" mode

In this mode the instrument shows the below screens according to the settings made as
per paragraph 8.1.

27.09.00 17:35:12

ENERGY

SINGLE PHASE

Ea1 = 0.000 kWh

Erc1 = 0.000 kVARh

Eri1 = 0.000 kVARh

P1 = 36.38 kW

Q1 = 6.375 kVAR

S1 = 36.94 kVA

dpf1 = 0.98 i

Meas Time: 00:00:00

MEAS

PG- PG+

Example of screen


The symbols used are described in Tab. 4.
For eventual messages displayed see Appendix 1 – MESSAGES DISPLAYED.
Following keys are enabled:

F2:

to start / stop immediately a

direct energy measurement. The

energy counters will start increasing proportionally to the active
power absorbed by the load.
The results obtained cannot be memorised.
If the active power is negative the counters will not increase.

F3/F4:

to pass to previous/next function respectively.

SAVE:

to save in the instrument memory a record of “Smp” type (see
paragraph 9.2) containing the instantaneous values of voltage and
current present on the instrument inputs. This function is disabled
during a recording.

ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the

displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word

HOLD

is displayed.

When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.

MENU:

to enter in the

MENU mode and change the instrument settings (see

paragraph 8.1 and 8.2). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.

START/STOP: to

record

selected parameters according to the instrument’s settings

(see chapter 10).

Advertising