General description, Caution – HT instruments SIRIUS89N User Manual

Page 8

Advertising
background image

SIRIUS89N

EN - 6

2. GENERAL DESCRIPTION

2.1. INTRODUCTION
Dear Customer, we thank you for your patronage. The instrument you have just purchased
will grant you accurate and reliable measurements provided that it is used according to the
present manual’s instructions.
The instrument was designed to grant the user the utmost safety conditions thanks to a
new concept assuring double insulation and over voltage category III.

2.2. FUNCTIONS
The instrument is able to perform eh following test:

LOW

Ω:

Continuity Test of Protection and Equalising conductors with test current
higher than 200mA and open circuit voltage ranging from 4V to 24V.

M

Ω:

Measurement of insulation resistance with DC test voltage 50V, 100V,
250V, 500V or 1000V.

RCD:

Measurement on common and/or selective RCDs AC type (

) and A

type (

) of the following parameters:

Tripping

time.

Tripping

current.

Contact voltage (U

t

).

Global earth resistance (R

a

).

Under this mode the instrument can measure the overall earth resistance
without causing RCD tripping.

LOOP

: Measurement of line and fault loop impedance with calculation of

prospective short circuit current, Measurement of fault loop impedance
between phase and earth and Global Earth resistance measurement
without RCD tripping and calculation of prospective short circuit current,
Indication of phase rotation sequence

EARTH

Measurement of Earth Resistance and Resisivity using Earth rods.

AUX:

Measurement and Recording of leakage current or environmental values
(temperature, humidity, Air Speed, Illuminance and Sound level).

ANALYZER: The Instrument allows the following operations:

Display in real time the electrical parameters of a single phase
systems and the harmonic analysis of voltage and current.

Conduct a direct Energy measurement (without memorizing).

Memorize (pressing SAVE key) the sampled values of the Parameters
present at instrument input generating a "Smp" record inside
instrument memory.

It will be possible to analyze the memorized

data ONLY by transferring it to a PC.

Record simultaneously (pressing the START key after a proper
setting): RMS values of voltage, current, corresponding harmonics,
active, reactive and apparent powers, power factors and cos

ϕ, active,

reactive and apparent energies, voltage anomalies (voltage sag and
surge) with 10ms resolution.

It will be possible to analyze the

recorded data ONLY by transferring them to a PC.


CAUTION

Please note the difference between

memorize and record. These terms

will be used repeatedly in this manual. Please focus on their definitions and
distinctions.

Advertising