HT instruments SIRIUS89N User Manual

Page 37

Advertising
background image

SIRIUS89N

EN - 35

RCD 05.06.01



1800


FRQ=50.0Hz Ut= 54V
VP-N=234V VP-PE= 34V

o UT NOT OK

R

A

30mA

50V

!

The instrument doesn't
detect an efficient
protection circuit.

FUNC

IdN RCD UL

Using the R

A

function,

if a contact voltage

U

t

higher than the
selected limit (U

L

) is

detected the instrument

emits

a long sound

signal at the end of the
test and displays the
screen alongside.

The test can be stored pressing the

SAVE key twice (according to paragraph 9.1).



6.3.3.2. RCD

tripping "faulty cases"

RCD 05.06.01



- - -

ms


FRQ=50.0Hz Ut= ---V
VP-N=231V VP-PE= 230V

o

RCD TRIPS

x1 30mA

50V

!

If the RCD trips during
the preliminary test
performed before the
test (independently from
the working mode) the
instrument displays the
screen alongside.

FUNC

IdN RCD UL

The RCD trips too early.
Check if the RCD Nominal
Current is correct.
Some leakage currents
may be present in the
installation. Disconnect all
the loads connected
downstream the RCD.

THE PREVIOUS RESULTS CAN'T BE SAVED.

RCD 05.06.01

RCD tripping time.



o

487

ms


FRQ=50.0Hz Ut= 1V
VP-N=231V VP-PE= 230V

o

TIME NOT OK

x1 30mA

50V

!

ATTENTION: the tripping
time is higher than the
standard limit.

FUNC

IdN RCD UL

In the tests MAN x1, x2,
x5 and AUTO (during x1
and x5 tests), if the RCD
trips to separate the
circuit within a time not
complying with the limits
reported in Table 3, the
instrument emits

a long

acoustic signal at the
end of the test and
displays the values
alongside.

The test can be stored pressing the

SAVE key twice (according to paragraph 9.1).