HT instruments SIRIUS89N User Manual

Page 53

Advertising
background image

SIRIUS89N

EN - 51

6.5.2. Measurement procedure and results of "

ρ" mode

1. Select

ρ

measurement mode by means of the F1 key.

2. Select the distance

d between the earth rods by means the F3 and F4 keys.

3. Connect the 4 Black, Red, Green and Blue connectors of the single cables in the

corresponding input terminals of the instrument

B1, B2, B3, B4.

Instrument connection for Earth resistivity measurement

4. Press the

START key. The instrument starts the test.

EARTH 05.06.01

Earth Resistivity value
expressed in

Ωm.

Voltage value of electrical
noise

Number of Test


1.77

m

Vd= 1V




Test:04

ρAVG=0.74Ω


ρ DIST= 2m!

At the end of the test
the instrument emits a
double sound signal
indicating that the
test is correctly
terminated

and

displays the values
alongside.

FUNC CLR

Average Value of Earth
Resistivity calculated over the
Number of Test displayed.

"

ρ" Working mode


5. The instrument will show automatically the Average value of the Earth Resistivity

calculate over the tests performed. Press

F2 to RESET this value and the number of

Test.

This result can be stored pressing the

SAVE key twice (according to paragraph 9.1).



START

STOP