EN - 19

6.2. M

: INSULATION RESISTANCE MEASUREMENT WITH 50V, 100V, 250V,

500V, 1000V TEST VOLTAGE

The measurement comply with IEC 61557-2 and VDE 0413 part 1.

CAUTION

Before effecting the insulation test make sure that the circuit under test is
not energised and all the loads are disconnected.


Turn the

switch on M

Ω position.


The key

F1 permits to select one of the following measuring modes:

Mode "

MAN" (Manual mode). Recommended test.

Mode "

TMR" (Timer mode: test duration depends on the selected interval

from 10 to 999 seconds). This test can be executed when the test
required a defined duration.


6.2.1. Measurement Procedure

1. Select the desired mode by means of the

F1 key.

2. Connect the test leads to the instrument input terminals

B1 and B4 respectively,

Example: insulation measurement between phase and
earth in an electrical installation using untied cables.

Example: insulation measurement between
phase and earth in an electrical installation

using the shuko cable.

3. If the cables supplied with the instrument are not long enough for the measurement

you can extend the blue cable.

4. Connect the instrument terminals to the object which is to be submitted to the

insulation test

after de-energizing the circuit under test and all the relative

loads (see previous picture).

5. By means of

F2 select the test voltage suitable for the type of test to be carried

out (see Table1). The values to be selected are:

• 50V (test on telecommunication systems)

• 100V

• 250V

• 500V

• 1000V