5.4. RESET

This option re-establishes the initial settings of the instrument in

ANALYZER function.


The “Current Range” parameter it is not modified by Reset command

The initial settings of the instrument consist of:

ANALYZER CONFIG:

System: SINGLE
Frequency: not

modified

Current range:

not modified

Clamp type:

not modified

Transforming ratio of voltmetric transformers:

1

Password: OFF

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MAN
Integration period:

15min

Recording of harmonics:

ON

Recording of Voltage anomalies (Sag and Surge:

ON

Voltage Reference for Sag and Surge detection:

230V

Upper Limit for Sag and Surge detection:

6%

Lower Limit for Sag and Surge detection:

10%

Selected voltages:

V1

Selected voltage harmonics:

THD, 01, 03, 05, 07

Selected currents:

I1

Selected current harmonics:

THD, 01, 03, 05, 07

CO-GENERATION: OFF
Powers, Pf and cos

ϕ selected:

P1

Q1i
Q1c
S1
Pf1
DPf1
Energie: Ea1
Eri1
Erc1



The RESET command will not erase the instrument’s memory.