Caution – HT instruments SIRIUS89N User Manual

Page 30

Advertising
background image

SIRIUS89N

EN - 28

6.3.2.1. Results of "x½" mode

4. Press the

START key once to execute a test with Current waveform.

or

Press the

START key once to execute a test with 180° Current waveform.

CAUTION

Never disconnect the test leads when the message

"MEASURING" is

displayed.

RCD 05.06.01

The symbol

">" means that

the RCD did not trip.

Value of contact voltage

U

t

detected referred to the
rated value of the RCD
current set.

If the RCD

does NOT

trip the instrument emits
a

double sound signal

indicating the positive
outcome
of the test and
displays the screen
alongside.

OK: RCD passed the test.



> 999

ms


FRQ=50.0Hz Ut= 1V
VP-N=231V VP-PE=231V

RCD OK

x1/2 30mA

50V

!

FUNC

IdN RCD UL

Contact Voltage Limit value

Working mode

RCD nominal current

RCD type

The test can be stored pressing the

SAVE key twice (according to paragraph 9.1).


6.3.2.2. Results of "x1, x2, x5" mode

4. Press the

START key once to execute a test with Current waveform.

or

Press the

START key once to execute a test with 180° Current waveform.

CAUTION

Never disconnect the test leads when the message

"MEASURING" is

displayed.

RCD 05.06.01

Tripping time (expressed in
milliseconds).

Value of contact voltage

U

t

detected referred to the
rated value of the RCD
current set.

OK: RCD passed the test.

If the tripping time is
within the limits reported
in Table 3, the
instrument emits a
double sound signal
indicating the positive
outcome
of the test and
displays the screen
alongside.



49

ms


FRQ=50.0Hz Ut= 2V
VP-N=231V VP-PE=231V

RCD OK

x1 30mA

50V

!

FUNC

IdN RCD UL

Contact Voltage Limit value

Working mode

RCD nominal current

RCD type

The test can be stored pressing the

SAVE key twice (according to paragraph 9.1).

START

STOP

START

STOP