6.4.3. Measurement procedure and results of "P-P" mode

1. Select

P-P mode by means of the F1 key.

2. Connect the Black, Green and Blue connectors of the three-terminal shuko cable or

of the split cables to the corresponding input terminals of the instrument

B1, B3, B4

Instrument connection for P-P test in a 400V three-phase system

3. Connect the shuko plug into a 230V 50Hz socket or the crocodiles to the

conductors of the three-phase system (see previous pictures).

4. If possible disconnect all low impedance loads downstream the point at which

the measurement is to be taken, as such impedance would be in parallel with
the line impedance to be measured.

5. Press the

START key. The instrument starts the test.


CAUTION

The P-P measurement in a 400V system make flow a test current of 11.5A
approx. This may cause the tripping of magnetic protection switch with nominal
value lower than 10A. If necessary effect the test upstream the switch. Never
disconnect the test leads when the message

"MEASURING" is displayed.

LOOP 05.06.01

Value of phase to phase
impedance expressed in

Ω.

Value of the phase to phase
prospective short circuit
current expressed in Ampere
calculated according to the
following formula.

At the end of the test
the instrument emits a
double sound signal
indicating that the test
is correctly
terminated

and

displays the values
alongside.


0.57

701A



FRQ=50.0HZ
VP-P=402V VP-PE=231V



P-P

!

Working mode

FUNC Z2

Formula for calculation of prospective short circuit current:

PP

N

CC

Z

U

I

=

where U

N

= phase to phase voltage

127 if V

meas

≤ 150

230 if 150V< V

meas

≤260

400 if V

meas

> 260


This result can be stored pressing the

SAVE key twice (according to paragraph 9.1).