HT instruments SIRIUS89N User Manual

Page 45

Advertising
background image

SIRIUS89N

EN - 43

LOOP 05.06.01

Value of phase to Earth
Resistance expressed in

Ω.

Effective value of the phase
to Earth prospective short
circuit current expressed in
Ampere calculated according
to the following formula..

At the end of the test
the instrument emits a
double sound signal
indicating that the test
is correctly
terminated

and

displays the values
alongside.


2

115A



Freq=50.0HZ
VP-N=231V Vp-PE=231V


R

A

!

Working mode

FUNC

Formula for calculation of prospective short circuit current:

PE

N

CC

Z

U

I

=

where U

N

= Nominal phase to neutral voltage =

127 if V

meas

≤150

230 if 150V< V

meas

≤250

This result can be stored pressing the

SAVE key twice (according to paragraph 9.1).



6.4.6. Measurement procedure and results of "

" mode

1. Select mode by means of the

F1 key.

2. Connect the Black, Red and Green connectors of the split cables to the

corresponding input terminals of the instrument

B1, B2, B3.

Instrument connection for Phase Sequence Detection in a 400V three-phase system

3. Press the

START key to execute a test.


LOOP 05.06.01

Phase Sequence OK

Value of the Phase to Phase
Voltage


RST


FRQ=50.0HZ VR-S=391V
VS-T=401V VT-R=399V

OK

!

At the end of the test
the instrument emits a
double sound signal
indicating that the test
is correctly
terminated

and

displays the values
alongside.

FUNC

Working mode

This result can be stored pressing the

SAVE key twice (according to paragraph 9.1).

START