HT instruments SIRIUS89N User Manual

Page 77

Advertising
background image

SIRIUS89N

EN - 75

8.4.3. "HARM" mode
Selecting the HARM mode the screen below will be displayed according to the settings
made as per paragraph 8.1. The screen show the harmonics (see paragraph 16.11) of the
voltage.

Example of screen


The symbols used are described in Tab. 1. For eventual messages displayed see
Appendix 1 – MESSAGES DISPLAYED. The displayed histograms represent the harmonic
content of the voltage under test. The value of the first harmonic h01 (fundamental at
50Hz) is not represented in scale along with the other harmonics in order to maximize the
display of the latter. In case both voltage and current are connected to the instrument
inputs, eventual negative values of the harmonics (therefore represented under the
horizontal axis), indicate that such voltage harmonics are “generated” by the load.
Following keys are enabled:

F3, F4:

to move the cursor of the selected harmonic leftwards and rightwards
respectively. At the same time the values relevant to the order no. of
the selected harmonic and to the corresponding absolute and relative
values (calculated on the basis of the fundamental) are updated.

F2:

to display the page of the harmonics h01

÷ h24 (symbol h24) or that

of the harmonics h25

÷ h49 (symbol h49).

ESC:

to return back to METER mode (see paragraph 8.4.2).

SAVE:

to save in the instrument memory a record of “Smp” type (see
paragraph 9.2) and the instantaneous values of voltage and current
present on the instrument inputs. This function is disabled during a
recording.

ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the

displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word

HOLD

is displayed.

When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.

MENU:

to enter in the

MENU mode and change the instrument settings (see

paragraph 8.1 and 8.2). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.

START/STOP: to

record

selected parameters according to the instrument’s settings

(see chapter 10).

27.09.00 17:35:12

V1 = 230.2 V

h03 = 10.2 V

h03 = 4.3 %

ThdV = 11.0 %

h49