HT instruments SIRIUS89N User Manual

Page 95

Advertising
background image

SIRIUS89N

EN - 93

START-UP

ANALYZER CONFIG:

All the parameters:

unmodified

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MANU
Integration period:

5sec

Recording of harmonics:

ON

Recording of Voltage anomalies (voltage Dips and Surge) :

ON

Voltage Reference for Dips and Surge detection:

230V

Upper Limit for Dips and Surge detection:

6%

Lower Limit for Dips and Surge detection:

10%

Selected voltages:

V1

Selected voltage harmonics:

THD, 01, 03, 05, 07, 09, 11, 13, 15

Selected currents:

I1

Selected current harmonics:

THD, 01, 03, 05, 07, 09, 11, 13, 15

CO-GENERATION: OFF
Selected powers, Pf and cos

ϕ:

P1, Q1i, Q1c, S1, Pf1, dpf1

Energies:

Ea1, Eri1, Erc1

POWER & ENERGY

ANALYZER CONFIG:

All the parameters:

unmodified

RECORDER CONFIG:

Start:

MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)

Stop: MANU
Integration period:

15min

Recording of harmonics:

OFF

Recording of Voltage anomalies (voltage Dips and Surge) :

OFF

Selected voltages:

V1

Selected currents:

I1

CO-GENERATION: ON
Selected powers, Pf and cos

ϕ:

P1, Q1i, Q1c, S1, Pf1, dpf1

Energies:

Ea1, Eri1, Erc1


By pressing

START/STOP the recording of the selected parameters is started according to

the settings made for each Typical Configuration. The rotary switch position doesn’t affect
the recording setting.