Z=----- ω, Caution, No imp57 – HT instruments SIRIUS89N User Manual

Page 39

Advertising
background image

SIRIUS89N

EN - 37

6.4. LOOP :

MEASUREMENT OF LINE IMPEDANCE, FAULT LOOP
IMPEDANCE, PROSPECTIVE SHORT CIRCUIT CURRENT
CALCULATION AND PHASE SEQUENCE INDICATOR

Turn the

switch on LOOP

position.



The

F1 key permits to select one of the following measuring modes:

Mode

"

P-N" (the instrument measures the impedance between the phase

and neutral conductors and calculates the phase to neutral prospective
short circuit current).

Mode "

P-P" (the instrument measures the impedance between two

phase conductors and calculates the phase to phase prospective short
circuit current).

Mode "

P-PE" (the instrument measures the impedance between the

phase and protective conductors and calculates the phase to earth
prospective short circuit current).

Mode "

R

A

"

(the instrument measures the impedance between the

phase and protective conductors with a test current of 15mA in order to
avoid RCD tripping and calculates the phase to earth prospective short
circuit current).

Mode

"

" (the instrument detect the Phase Sequence in a three-phase

system).

CAUTION

Never disconnect the test leads when the message

"MEASURING" is

displayed.

6.4.1. High resolution Impedance measurement (0.1m

)

The instrument is connectable to an external

optional accessory (IMP57) useful for high

resolution impedance measurement close to a power transformer.
The high Resolution impedance measurement is available inside the

LOOP P-P, P-N, P-PE

modes by mean

Un/I∆n key. If You enable the High Resolution Impedance Measurement

mode without connecting IMP57 the following screen will be displayed (e.g: Loop P-N):

LOOP

29.01.04

Z=-----

R=-----

Ω X=-----Ω

IkSTD=----A

V1-2= 0V FRQ= 0.0Hz

NO IMP57


P-N Z2

FUNZ ZSTD ICAL RMT


For further details regarding IMP57 use and technical characteristics please refer to IMP57
user's manual or HT web site