HT instruments SIRIUS89N User Manual

Page 55

Advertising
background image

SIRIUS89N

EN - 53

EARTH 05.06.01


- - -

Vd= 1V



Test:04
RAVG=0.74

o Rp HIGH


3-W

!

FUNC CLR

Message "Rp": Check
Auxiliary Earth rods.

The message "Rp
high
" indicates that the
instrument can't
measure correctly the
Voltage from Auxiliary
Earth rod. Check that
the terminals are
correctly connected and
the Auxiliary earth rod
connected to B2 (red
conductor) has not been
inserted in a pebbly or
poor conductive ground.
If necessary pour some
water around the rod.

EARTH 05.06.01


- - -

Vd= 1V




Test:04
RAVG=0.74

o Rp and Rc HIGH


3-W

!

FUNC CLR

Message "Rp and Rc HIGH":
Check Auxiliary Earth rods.

The message "Rp and
Rc high
" indicates that
the instrument can't
measure correctly the
Voltage from Auxiliary
Earth rod and can't
flowe the minimum
current for
measurement. Check
that the terminals are
correctly connected.
Check if the Auxiliary
earth rod connected to
B2 (red conductor) and
B4(blue conductor) has
not been inserted in a
pebbly or poor
conductive ground. If
necessary pour some
water around the rod.

THE PREVIOUS RESULTS CANNOT BE SAVED.