SIRIUS89N

EN - 24

6.3.

RCD: TEST ON "A" AND "AC" RCDS TYPE


The test is executed according to IEC61557-6, EN61008, EN61009, EN60947-2 B 4.2.4
and VDE 0413 part 6.

CAUTION

The automatic check of the RCD features causes the tripping of the RCD itself.
Therefore

check that all devices connected downstream the RCD under

test are not damaged by power off. Possibly disconnect all the loads
connected downstream the RCD as they could add additional leakage currents
to the instrument ones and so making the test results void.


Turn the

switch on RCD position:



The

F1 key permits to select one of the following measuring mode (which can

be shown cyclically when pressing the key):

Mode "

AUTO" (the instrument effects the test automatically with a

leakage current equal to half, once and five times the value of the rated
current set). Recommended test.

Mode

"

x ½" (the instrument effects the test with a leakage current equal

to half the value of the rated current set).

Mode "

x 1" (the instrument effects the test with a leakage current equal

to once the value of the rated current set ).

Mode "

x 2" (the instrument effects the test with a leakage current equal

to twice the value of the rated current set).

Mode "

x 5" (the instrument effects the test with a leakage current equal

to five times the value of the rated current)

Mode " " (the instrument effects the test with a ramp growing leakage

current. Use this test to measure the tripping current).

Mode

"R

A

" (the instrument effects the test with a leakage current

equal to half the value of the selected rated current and calculates the
contact voltage as well as the R

a

earth resistance).

N.B. The AUTO mode execute automatically test with phase 0° and 180°

RCD Type

0° Current Waveform

180° Current Waveform

AC type

A type

According to standard praxis it is recommended to effect RCD test both with
phase 0° and with phase 180° even with no AUTO modes. If the RCD under
test is A type (which means sensitive to both AC and unidirectional pulsing

Advertising