EN - 30

6.3.2.4. Results of "RAMP " mode


4.

Press the

START key once to execute a test with Current waveform.

or


Press

the

START key once to execute a test with 180° Current waveform.

The instrument generates a leakage current growing step by step for a given
time interval.


CAUTION

Never disconnect the test leads when the message

"MEASURING" is

displayed.

Tripping Current

RCD 05.06.01

Tripping time (expressed in
milliseconds).

Value of contact voltage

U

t

detected referred to the
rated value of the RCD
current set.

OK: RCD passed the test.


27

mA

35ms


FRQ=50.0Hz Ut= 1V
VP-N=231V VP-PE=231V

RCD OK

30mA

50V

!

At the end of the test if
the RCD tripping current
is lower than I

∆n

(Type

AC) or 1.4I

∆n

(Type A

with I

∆n

>10mA) or 2I

∆n

(Type A with I

∆n

≤10mA),

the instrument emits a
double sound signal
indicating the positive
outcome of the test and
displays the screen
alongside.

FUNC

IdN RCD UL

Contact Voltage Limit value

Working mode

RCD nominal current

RCD type



The test can be stored pressing the

SAVE key twice (according to paragraph 9.1).


START

STOP