3.4.25.2 PUE/DCiE Trending

Now that the RIM-1000 is generating PUE/DCiE information, it can log long-term trending data. The trending program can log 3840
entries. Once 3840 entries have been logged, the system will eliminate 40 entries at a time and overwrite the data, from oldest
to newest. Long-term trending is the most effective way to use PUE/DCiE data.

Format Trends

1. On the RIM-1000 interface, go to Configuration>Trends.

2. You may already have some trending tasks operating on the RIM-1000. Select the next available index number. Use the following

points to trend your data:

3. Select Modbus/SNMP as the type.

4. Now, determine the interval at which you wish to trend the data. The interval is selectable, from a 1 minute interval to an

8 hour interval - it just depends how detailed you’d like your data to be. At a 1 minute interval, the RIM-1000 will store approximately
2.5 days worth of data before it begins to overwrite. At an 8 hour interval, the RIM-1000 will store approximately 3.5 years of data
before it begins to overwrite the oldest data.

Figure 3.47 Establish Trending

Point Value

Trended Data

629

DCiE 1

630

PUE 1

631

DCiE 2

632

PUE 2

633

DCiE 1 + 2

634

PUE 1 + 2

635

Summary 1

636

Summary 2