3.4.12 Modem/Phone Numbers/Pagers

Use this page to instruct the RIM-1000 when, how, and whom to call when an alarm occurs The top of this configuration page
allows users to configure the RIM-1000 internal modem which must be ordered separately (P/N 60104-001). The section of the page
below the ruled line allows users to configure phone numbers can be notified when the RIM-1000 goes into alarm condition.

Figure 3.25 Modem/Phone Numbers/Pagers Configuration Page

Table 3.14 Modem/Phone Numbers/Pagers Configuration Options

Option

Description

Initialization String

A maximum of 38 characters. &c1 and &d3 are mandatory. s0=1
sets the modem to answer after one ring. s0=0 disables the auto
answer and prevents dial-in access.

Default: at&c1&d3s0=1

Dial Prefix

Should be a specific Hayes compatible command or dial modifier
depending on pager requirements. It is also limited to 38
characters.

Default: atdt

Pager Deliveries

Designates the number of times (0-255) the pager is called until the
alarm is acknowledged. Pagers are called in sequence.

Example: If Pager Deliveries is set to 3 and pagers 1, 7, and 10 are
programmed to be notified, the RIM-1000 dials 1, 7, 10, 1, 7, 10, 1, 7, 10.
As soon as the alarm is acknowledged, the RIM-1000 quits dialing the
pagers with that particular access code. Pagers with different access
codes are still dialed.

Pager Interval

Determines the number of minutes to wait between redials.

Advertising