Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual

Page 141

Advertising
background image

Remote Infrastructure Management System - Version 1.0 / July 2014

Chatsworth Products, Inc. (CPI) • 800-834-4969

141

Table 4.6 Individual Modbus Register Configuration Options

Option

Description

Register Acquisition

Register/Offset

Enter the Register Number for the data to be read. The Register
Number is located on the Slave Units Modbus Register Map; see
4.7.1, “Slave Register Map” on page 146.

Register Type

Select the Data Type of the Register.
• Unsigned Int
• Signed Int
• Long
• Float
• Alarm Bit/ ON= ALARM
• Alarm Bit/ OFF=ALARM
• Status Bit - No Log
• Status Bit - Logged
• Coil Status

• Input Status

NOTE: Refer to the manufacturer’s equipment guide for the register
numbers and the data type.

Scaler

Select a multiplier for the data value.

Offset

Allows users to fine-tune analog values. Offset adjustment may be
required by certain manufacturers.

Bitflag

Applies to Data Types, Alarm Bit, Status Bit-Logged and Status Bit -
No Log. Selects which bit is read from the 16 or 32 bit register
value.

Registers

Designate the correct type of read holding/input register.

Word Order

Applies to Data Types Long and Float. Long and Float Data Types
read two consecutive registers. The word order selects if the first
register is the larger or smaller part of the number.

Label

Enter a label to describe the Data Point.

UOM/Map Label

Specify the unit of measure you are using for this specific point.

Log Index

Applies to Data Types Signed Int, Unsigned Int, Long and Float.
The RIM-1000 has 232 entries reserved for logging (Min, Hour and Day
Logs). Enter a value of 1 to 232 if the point is to be internally logged
on the RIM-1000. Each register to be logged requires a unique entry number.

OUM Conversion

Convert a unit of measure from the way it is communicated by the
device to the way you would like to have it displayed.
• deg C - deg F (1,10,100,1000 Scale)
• deg C - deg F (1/32 Scale
• kPa - PSI (1/8, 1/28 Scale)

Alarm Thresholds:
High 2, High1, Low1, Low2

Set high and low - or major and minor - thresholds for alarm analog
alarm values being read by these points.

Advertising