4.2.1

EIA-232

The EIA-232 COM Port 1 on the RIM-1000 is used to connect the RIM-1000-as a Modbus Master-to one Modbus Slave device, or
it is used to connect a Modbus Master device to the RIM-1000 as a Modbus Slave. The Modbus EIA-232 (DTE) is active over COM1

(DB9 male connector). The EIA-232 port allows communications between the RIM-1000 and one other device (point to point

connection). The EIA-232 port has maximum cable length of 50 feet (15.2m).

Table 4.1 COM1 DB9 Male Pin Out

Figure 4.1 RIM-1000 Modbus EIA-232 Connection to an EIA-232 DCE Device

Pin

Description

1

Data Carrier Detect

2

Receive Data

3

Transmit Data

4

Data Terminal Ready

5

Signal Ground

6

No Connection

7

Request to Send (internally connected to Pin 8)

8

Clear to Send (internally connected to Pin 7)

9

No Connection