Table C.1 Analog Input 4-20mA Reference Chart (continued)

Product #

Transducer Type

Range

Gain

Offset

Voltage

PT300

Voltage - Single Phase

0 - 300 Amps

75

-75

3PT300

Voltage - Three Phase

0 - 300 Amps

75

-75

PT600

Voltage - Single Phase

0 - 600 Amps

150

-150

3PT600

Voltage - Three Phase

0 - 600 Amps

150

-150

Distance Read Leak Detection

LD5000

Leak Detection
4-10mA Output
(Calculated in ft/m)

0 - 500 ft / 152m

143

-179

0 - 1000 ft / 305m

286

-357

0 - 1500 ft / 457m

429

-536

0 - 2000 ft / 610m

571

-714

0 - 2500 ft / 762m

714

-893

0 - 3000 ft / 914m

857

-1071

0 - 3500 ft / 1067m

1000

-1250

0 - 4000 ft / 1219m

1143

-1429

0 - 4500 ft / 1372m

1286

-1607

0 - 5000 ft / 1524m

1429

-1786

LD5100

Leak Detection
4-20mA Output
(Calculated in ft/m)

0 - 1000 ft / 305m

250

-250

0 - 2500 ft / 762m

625

-625

0 - 5000 ft / 1524m

1250

-1250