Chatsworth Products, Inc. (CPI) • 800-834-4969

41

3.4. Configuration

The Configuration page allows authorized users with administrator or read-write privileges to adjust the RIM-1000 settings. Each link on
the Configuration page displays more information about specific configuration settings.

Figure 3.4 Configuration Page

NOTE: If any of the fields within the sub-menus are edited, be sure to click the Submit Changes button to save the changes. If you
edit the fields and navigate from the web pages without clicking the Submit Changes button, all changes will be lost.

3.4.1 Inputs and Relays

Inputs and Relays allows users to program specific parameters for each RIM-1000 input and relay. Only installed inputs and
relays are displayed.

Different RIM-1000 models allow different numbers of inputs and relays. A1U RIM-1000 will include the Main Board inputs, and
has room for one expansion card - either an A card or a C card.

A 2U RIM-1000 allows 4 expansion cards to be added to the unit - each expansion card slot can be outfitted with either an A card
or a C card.

• Main Board Inputs 1-8 - Every RIM-1000 has a main board. This board provides 8 inputs configurable as analog 4-20mA or digital NO/NC.

• Expansion Card A Inputs and Outputs- adds an additional 12 inputs, configurable as analog 4-20mA, 0-5V, 0-10V or digital NO

(cannot be configured as NC), as well as 8 form C relay outputs.

• Expansion Card C Inputs - adds an additional 24 digital NO/NC inputs. There are no additional relay outputs on a C card